He comprado este SAI/UPS al ser compatible con GNU/Linux gracias al proyecto NUT (Network UPS Tools).
Dejo a continuación mis archivos de configuración incluyendo toda la documentación comentada que viene incluida en estos ya que es donde se explica todo lo referente a las distintas opciones de configuración, y ante cualquier duda me comentáis.
# Network UPS Tools: example nut.conf
#
##############################################################################
# General section
##############################################################################
# The MODE determines which part of the NUT is to be started, and which
# configuration files must be modified.
#
# This file try to standardize the various files being found in the field, like
# /etc/default/nut on Debian based systems, /etc/sysconfig/ups on RedHat based
# systems, ... Distribution's init script should source this file to see which
# component(s) has to be started.
#
# The values of MODE can be:
# - none: NUT is not configured, or use the Integrated Power Management, or use
# some external system to startup NUT components. So nothing is to be started.
# - standalone: This mode address a local only configuration, with 1 UPS
# protecting the local system. This implies to start the 3 NUT layers (driver,
# upsd and upsmon) and the matching configuration files. This mode can also
# address UPS redundancy.
# - netserver: same as for the standalone configuration, but also need
# some more network access controls (firewall, tcp-wrappers) and possibly a
# specific LISTEN directive in upsd.conf.
# Since this MODE is opened to the network, a special care should be applied
# to security concerns.
# - netclient: this mode only requires upsmon.
#
# IMPORTANT NOTE:
# This file is intended to be sourced by shell scripts.
# You MUST NOT use spaces around the equal sign!
MODE=standalone
# Network UPS Tools: example ups.conf
#
# --- SECURITY NOTE ---
#
# If you use snmp-ups and set a community string in here, you
# will have to secure this file to keep other users from obtaining
# that string. It needs to be readable by upsdrvctl and any drivers,
# and by upsd.
#
# ---
#
# This is where you configure all the UPSes that this system will be
# monitoring directly. These are usually attached to serial ports, but
# USB devices and SNMP devices are also supported.
#
# This file is used by upsdrvctl to start and stop your driver(s), and
# is also used by upsd to determine which drivers to monitor. The
# drivers themselves also read this file for configuration directives.
#
# The general form is:
#
# [upsname]
# driver = <drivername>
# port = <portname>
# < any other directives here >
#
# The section header ([upsname]) can be just about anything as long as
# it is a single word inside brackets. upsd uses this to uniquely
# identify a UPS on this system.
#
# If you have a UPS called snoopy, your section header would be "[snoopy]".
# On a system called "doghouse", the line in your upsmon.conf to monitor
# it would look something like this:
#
# MONITOR snoopy@doghouse 1 upsmonuser mypassword master
#
# It might look like this if monitoring in slave mode:
#
# MONITOR snoopy@doghouse 1 upsmonuser mypassword slave
#
# Configuration directives
# ------------------------
#
# These directives are used by upsdrvctl only and should be specified outside
# of a driver definition:
#
# maxretry: Optional. Specify the number of attempts to start the driver(s),
# in case of failure, before giving up. A delay of 'retrydelay' is
# inserted between each attempt. Caution should be taken when using
# this option, since it can impact the time taken by your system to
# start.
#
# The default is 1 attempt.
#
# retrydelay: Optional. Specify the delay between each restart attempt of the
# driver(s), as specified by 'maxretry'. Caution should be taken
# when using this option, since it can impact the time taken by your
# system to start.
#
# The default is 5 seconds.
#
# These directives are common to all drivers that support ups.conf:
#
# driver: REQUIRED. Specify the program to run to talk to this UPS.
# apcsmart, bestups, and sec are some examples.
#
# port: REQUIRED. The serial port where your UPS is connected.
# /dev/ttyS0 is usually the first port on Linux boxes, for example.
#
# sdorder: optional. When you have multiple UPSes on your system, you
# usually need to turn them off in a certain order. upsdrvctl
# shuts down all the 0s, then the 1s, 2s, and so on. To exclude
# a UPS from the shutdown sequence, set this to -1.
#
# The default value for this parameter is 0.
#
# nolock: optional, and not recommended for use in this file.
#
# If you put nolock in here, the driver will not lock the
# serial port every time it starts. This may allow other
# processes to seize the port if you start more than one by
# mistake.
#
# This is only intended to be used on systems where locking
# absolutely must be disabled for the software to work.
#
# maxstartdelay: optional. This can be set as a global variable
# above your first UPS definition and it can also be
# set in a UPS section. This value controls how long
# upsdrvctl will wait for the driver to finish starting.
# This keeps your system from getting stuck due to a
# broken driver or UPS.
#
# The default is 45 seconds.
#
# synchronous: optional. The driver work by default in asynchronous
# mode (i.e *synchronous=no*). This means that all data
# are pushed by the driver on the communication socket to
# upsd (Unix socket on Unix, Named pipe on Windows) without
# waiting for these data to be actually consumed. With
# some HW, such as ePDUs, that can produce a lot of data,
# asynchronous mode may cause some congestion, resulting in
# the socket to be full, and the driver to appear as not
# connected. By enabling the 'synchronous' flag
# (value = 'yes'), the driver will wait for data to be
# consumed by upsd, prior to publishing more. This can be
# enabled either globally or per driver.
#
# The default is 'no' (i.e. asynchronous mode) for backward
# compatibility of the driver behavior.
#
# Anything else is passed through to the hardware-specific part of
# the driver.
#
# Examples
# --------
#
# A simple example for a UPS called "powerpal" that uses the blazer_ser
# driver on /dev/ttyS0 is:
#
# [powerpal]
# driver = blazer_ser
# port = /dev/ttyS0
# desc = "Web server"
#
# If your UPS driver requires additional settings, you can specify them
# here. For example, if it supports a setting of "1234" for the
# variable "cable", it would look like this:
#
# [myups]
# driver = mydriver
# port = /dev/ttyS1
# cable = 1234
# desc = "Something descriptive"
#
# To find out if your driver supports any extra settings, start it with
# the -h option and/or read the driver's documentation.
# Set maxretry to 3 by default, this should mitigate race with slow devices:
maxretry = 3
[salicru]
driver = blazer_usb
port = auto
desc = "Salicru SPS One"
# Network UPS Tools: example upsd configuration file
#
# This file contains access control data, you should keep it secure.
#
# It should only be readable by the user that upsd becomes. See the FAQ.
#
# Each entry below provides usage and default value.
# =======================================================================
# MAXAGE <seconds>
# MAXAGE 15
#
# This defaults to 15 seconds. After a UPS driver has stopped updating
# the data for this many seconds, upsd marks it stale and stops making
# that information available to clients. After all, the only thing worse
# than no data is bad data.
#
# You should only use this if your driver has difficulties keeping
# the data fresh within the normal 15 second interval. Watch the syslog
# for notifications from upsd about staleness.
# =======================================================================
# STATEPATH <path>
# STATEPATH /var/run/nut
#
# Tell upsd to look for the driver state sockets in 'path' rather
# than the default that was compiled into the program.
# =======================================================================
# LISTEN <address> [<port>]
# LISTEN 127.0.0.1 3493
# LISTEN ::1 3493
#
# This defaults to the localhost listening addresses and port 3493.
# In case of IP v4 or v6 disabled kernel, only the available one will be used.
#
# You may specify each interface you want upsd to listen on for connections,
# optionally with a port number.
#
# You may need this if you have multiple interfaces on your machine and
# you don't want upsd to listen to all interfaces (for instance on a
# firewall, you may not want to listen to the external interface).
#
# This will only be read at startup of upsd. If you make changes here,
# you'll need to restart upsd, reload will have no effect.
# =======================================================================
# MAXCONN <connections>
# MAXCONN 1024
#
# This defaults to maximum number allowed on your system. Each UPS, each
# LISTEN address and each client count as one connection. If the server
# runs out of connections, it will no longer accept new incoming client
# connections. Only set this if you know exactly what you're doing.
# =======================================================================
# CERTFILE <certificate file>
# CERTFILE /usr/local/ups/etc/upsd.pem
#
# When compiled with SSL support with OpenSSL backend,
# you can enter the certificate file here.
# The certificates must be in PEM format and must be sorted starting with
# the subject's certificate (server certificate), followed by intermediate
# CA certificates (if applicable_ and the highest level (root) CA. It should
# end with the server key. See 'docs/security.txt' or the Security chapter of
# NUT user manual for more information on the SSL support in NUT.
#
# See 'docs/security.txt' or the Security chapter of NUT user manual
# for more information on the SSL support in NUT.
# =======================================================================
# CERTPATH <certificate file or directory>
# CERTPATH /usr/local/ups/etc/cert/upsd
#
# When compiled with SSL support with NSS backend,
# you can enter the certificate path here.
# Certificates are stored in a dedicated database (splitted in 3 files).
# Specify the path of the database directory.
#
# See 'docs/security.txt' or the Security chapter of NUT user manual
# for more information on the SSL support in NUT.
# =======================================================================
# CERTIDENT <certificate name> <database password>
# CERTIDENT "my nut server" "MyPasSw0rD"
#
# When compiled with SSL support with NSS backend,
# you can specify the certificate name to retrieve from database to
# authenticate itself and the password
# required to access certificate related private key.
#
# See 'docs/security.txt' or the Security chapter of NUT user manual
# for more information on the SSL support in NUT.
# =======================================================================
# CERTREQUEST <certificate request level>
# CERTREQUEST REQUIRE
#
# When compiled with SSL support with NSS backend and client certificate
# validation (disabled by default, see 'docs/security.txt'),
# you can specify if upsd requests or requires client's' certificates.
# Possible values are :
# - 0 to not request to clients to provide any certificate
# - 1 to require to all clients a certificate
# - 2 to require to all clients a valid certificate
#
# See 'docs/security.txt' or the Security chapter of NUT user manual
# for more information on the SSL support in NUT.
# Network UPS Tools: Example upsd.users
#
# This file sets the permissions for upsd - the UPS network daemon.
# Users are defined here, are given passwords, and their privileges are
# controlled here too. Since this file will contain passwords, keep it
# secure, with only enough permissions for upsd to read it.
# --------------------------------------------------------------------------
# Each user gets a section. To start a section, put the username in
# brackets on a line by itself. To set something for that user, specify
# it under that section heading. The username is case-sensitive, so
# admin and AdMiN are two different users.
#
# Possible settings:
#
# password: The user's password. This is case-sensitive.
#
# --------------------------------------------------------------------------
#
# actions: Let the user do certain things with upsd.
#
# Valid actions are:
#
# SET - change the value of certain variables in the UPS
# FSD - set the "forced shutdown" flag in the UPS
#
# --------------------------------------------------------------------------
#
# instcmds: Let the user initiate specific instant commands. Use "ALL"
# to grant all commands automatically. There are many possible
# commands, so use 'upscmd -l' to see what your hardware supports. Here
# are a few examples:
#
# test.panel.start - Start a front panel test
# test.battery.start - Start battery test
# test.battery.stop - Stop battery test
# calibrate.start - Start calibration
# calibrate.stop - Stop calibration
#
# --------------------------------------------------------------------------
#
# Example:
#
# [admin]
# password = mypass
# actions = SET
# instcmds = ALL
#
#
# --- Configuring for a user who can execute tests only
#
# [testuser]
# password = pass
# instcmds = test.battery.start
# instcmds = test.battery.stop
#
# --- Configuring for upsmon
#
# To add a user for your upsmon, use this example:
#
# [upsmon]
# password = pass
# upsmon master
# or
# upsmon slave
#
# The matching MONITOR line in your upsmon.conf would look like this:
#
# MONITOR myups@localhost 1 upsmon pass master (or slave)
MAXAGE 15
STATEPATH /var/run/nut
LISTEN 127.0.0.1 3493
MAXCONN 1024
[admin]
password = Ahoravasylacascas-somugriento
actions = SET
instcmds = ALL
# Network UPS Tools: example upsmon configuration
#
# This file contains passwords, so keep it secure.
# --------------------------------------------------------------------------
# RUN_AS_USER <userid>
#
# By default, upsmon splits into two processes. One stays as root and
# waits to run the SHUTDOWNCMD. The other one switches to another userid
# and does everything else.
#
# The default nonprivileged user is set at compile-time with
# 'configure --with-user=...'.
#
# You can override it with '-u <user>' when starting upsmon, or just
# define it here for convenience.
#
# Note: if you plan to use the reload feature, this file (upsmon.conf)
# must be readable by this user! Since it contains passwords, DO NOT
# make it world-readable. Also, do not make it writable by the upsmon
# user, since it creates an opportunity for an attack by changing the
# SHUTDOWNCMD to something malicious.
#
# For best results, you should create a new normal user like "nutmon",
# and make it a member of a "nut" group or similar. Then specify it
# here and grant read access to the upsmon.conf for that group.
#
# This user should not have write access to upsmon.conf.
#
# RUN_AS_USER nut
# --------------------------------------------------------------------------
# MONITOR <system> <powervalue> <username> <password> ("master"|"slave")
#
# List systems you want to monitor. Not all of these may supply power
# to the system running upsmon, but if you want to watch it, it has to
# be in this section.
#
# You must have at least one of these declared.
#
# <system> is a UPS identifier in the form <upsname>@<hostname>[:<port>]
# like ups@localhost, su700@mybox, etc.
#
# Examples:
#
# - "su700@mybox" means a UPS called "su700" on a system called "mybox"
#
# - "fenton@bigbox:5678" is a UPS called "fenton" on a system called
# "bigbox" which runs upsd on port "5678".
#
# The UPS names like "su700" and "fenton" are set in your ups.conf
# in [brackets] which identify a section for a particular driver.
#
# If the ups.conf on host "doghouse" has a section called "snoopy", the
# identifier for it would be "snoopy@doghouse".
#
# <powervalue> is an integer - the number of power supplies that this UPS
# feeds on this system. Most computers only have one power supply, so this
# is normally set to 1. You need a pretty big or special box to have any
# other value here.
#
# You can also set this to 0 for a system that doesn't supply any power,
# but you still want to monitor. Use this when you want to hear about
# changes for a given UPS without shutting down when it goes critical,
# unless <powervalue> is 0.
#
# <username> and <password> must match an entry in that system's
# upsd.users. If your username is "monmaster" and your password is
# "blah", the upsd.users would look like this:
#
# [monmaster]
# password = blah
# upsmon master (or slave)
#
# "master" means this system will shutdown last, allowing the slaves
# time to shutdown first.
#
# "slave" means this system shuts down immediately when power goes critical.
#
# Examples:
#
# MONITOR myups@bigserver 1 monmaster blah master
# MONITOR su700@server.example.com 1 upsmon secretpass slave
# MONITOR myups@localhost 1 upsmon pass master (or slave)
# --------------------------------------------------------------------------
# MINSUPPLIES <num>
#
# Give the number of power supplies that must be receiving power to keep
# this system running. Most systems have one power supply, so you would
# put "1" in this field.
#
# Large/expensive server type systems usually have more, and can run with
# a few missing. The HP NetServer LH4 can run with 2 out of 4, for example,
# so you'd set that to 2. The idea is to keep the box running as long
# as possible, right?
#
# Obviously you have to put the redundant supplies on different UPS circuits
# for this to make sense! See big-servers.txt in the docs subdirectory
# for more information and ideas on how to use this feature.
MINSUPPLIES 1
# --------------------------------------------------------------------------
# SHUTDOWNCMD "<command>"
#
# upsmon runs this command when the system needs to be brought down.
#
# This should work just about everywhere ... if it doesn't, well, change it.
SHUTDOWNCMD "/sbin/shutdown -h +0"
# --------------------------------------------------------------------------
# NOTIFYCMD <command>
#
# upsmon calls this to send messages when things happen
#
# This command is called with the full text of the message as one argument.
# The environment string NOTIFYTYPE will contain the type string of
# whatever caused this event to happen.
#
# Note that this is only called for NOTIFY events that have EXEC set with
# NOTIFYFLAG. See NOTIFYFLAG below for more details.
#
# Making this some sort of shell script might not be a bad idea. For more
# information and ideas, see docs/scheduling.txt
#
# Example:
# NOTIFYCMD /bin/notifyme
# --------------------------------------------------------------------------
# POLLFREQ <n>
#
# Polling frequency for normal activities, measured in seconds.
#
# Adjust this to keep upsmon from flooding your network, but don't make
# it too high or it may miss certain short-lived power events.
POLLFREQ 5
# --------------------------------------------------------------------------
# POLLFREQALERT <n>
#
# Polling frequency in seconds while UPS on battery.
#
# You can make this number lower than POLLFREQ, which will make updates
# faster when any UPS is running on battery. This is a good way to tune
# network load if you have a lot of these things running.
#
# The default is 5 seconds for both this and POLLFREQ.
POLLFREQALERT 5
# --------------------------------------------------------------------------
# HOSTSYNC - How long upsmon will wait before giving up on another upsmon
#
# The master upsmon process uses this number when waiting for slaves to
# disconnect once it has set the forced shutdown (FSD) flag. If they
# don't disconnect after this many seconds, it goes on without them.
#
# Similarly, upsmon slave processes wait up to this interval for the
# master upsmon to set FSD when a UPS they are monitoring goes critical -
# that is, on battery and low battery. If the master doesn't do its job,
# the slaves will shut down anyway to avoid damage to the file systems.
#
# This "wait for FSD" is done to avoid races where the status changes
# to critical and back between polls by the master.
HOSTSYNC 15
# --------------------------------------------------------------------------
# DEADTIME - Interval to wait before declaring a stale ups "dead"
#
# upsmon requires a UPS to provide status information every few seconds
# (see POLLFREQ and POLLFREQALERT) to keep things updated. If the status
# fetch fails, the UPS is marked stale. If it stays stale for more than
# DEADTIME seconds, the UPS is marked dead.
#
# A dead UPS that was last known to be on battery is assumed to have gone
# to a low battery condition. This may force a shutdown if it is providing
# a critical amount of power to your system.
#
# Note: DEADTIME should be a multiple of POLLFREQ and POLLFREQALERT.
# Otherwise you'll have "dead" UPSes simply because upsmon isn't polling
# them quickly enough. Rule of thumb: take the larger of the two
# POLLFREQ values, and multiply by 3.
DEADTIME 15
# --------------------------------------------------------------------------
# POWERDOWNFLAG - Flag file for forcing UPS shutdown on the master system
#
# upsmon will create a file with this name in master mode when it's time
# to shut down the load. You should check for this file's existence in
# your shutdown scripts and run 'upsdrvctl shutdown' if it exists.
#
# See the config-notes.txt file in the docs subdirectory for more information.
# Refer to the section:
# [[UPS_shutdown]] "Configuring automatic shutdowns for low battery events"
# or refer to the online version.
POWERDOWNFLAG /etc/killpower
# --------------------------------------------------------------------------
# NOTIFYMSG - change messages sent by upsmon when certain events occur
#
# You can change the default messages to something else if you like.
#
# NOTIFYMSG <notify type> "message"
#
# NOTIFYMSG ONLINE "UPS %s on line power"
# NOTIFYMSG ONBATT "UPS %s on battery"
# NOTIFYMSG LOWBATT "UPS %s battery is low"
# NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
# NOTIFYMSG COMMOK "Communications with UPS %s established"
# NOTIFYMSG COMMBAD "Communications with UPS %s lost"
# NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"
# NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"
# NOTIFYMSG NOCOMM "UPS %s is unavailable"
# NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"
#
# Note that %s is replaced with the identifier of the UPS in question.
#
# Possible values for <notify type>:
#
# ONLINE : UPS is back online
# ONBATT : UPS is on battery
# LOWBATT : UPS has a low battery (if also on battery, it's "critical")
# FSD : UPS is being shutdown by the master (FSD = "Forced Shutdown")
# COMMOK : Communications established with the UPS
# COMMBAD : Communications lost to the UPS
# SHUTDOWN : The system is being shutdown
# REPLBATT : The UPS battery is bad and needs to be replaced
# NOCOMM : A UPS is unavailable (can't be contacted for monitoring)
# NOPARENT : The process that shuts down the system has died (shutdown impossible)
# --------------------------------------------------------------------------
# NOTIFYFLAG - change behavior of upsmon when NOTIFY events occur
#
# By default, upsmon sends walls (global messages to all logged in users)
# and writes to the syslog when things happen. You can change this.
#
# NOTIFYFLAG <notify type> <flag>[+<flag>][+<flag>] ...
#
# NOTIFYFLAG ONLINE SYSLOG+WALL
# NOTIFYFLAG ONBATT SYSLOG+WALL
# NOTIFYFLAG LOWBATT SYSLOG+WALL
# NOTIFYFLAG FSD SYSLOG+WALL
# NOTIFYFLAG COMMOK SYSLOG+WALL
# NOTIFYFLAG COMMBAD SYSLOG+WALL
# NOTIFYFLAG SHUTDOWN SYSLOG+WALL
# NOTIFYFLAG REPLBATT SYSLOG+WALL
# NOTIFYFLAG NOCOMM SYSLOG+WALL
# NOTIFYFLAG NOPARENT SYSLOG+WALL
#
# Possible values for the flags:
#
# SYSLOG - Write the message in the syslog
# WALL - Write the message to all users on the system
# EXEC - Execute NOTIFYCMD (see above) with the message
# IGNORE - Don't do anything
#
# If you use IGNORE, don't use any other flags on the same line.
# --------------------------------------------------------------------------
# RBWARNTIME - replace battery warning time in seconds
#
# upsmon will normally warn you about a battery that needs to be replaced
# every 43200 seconds, which is 12 hours. It does this by triggering a
# NOTIFY_REPLBATT which is then handled by the usual notify structure
# you've defined above.
#
# If this number is not to your liking, override it here.
RBWARNTIME 43200
# --------------------------------------------------------------------------
# NOCOMMWARNTIME - no communications warning time in seconds
#
# upsmon will let you know through the usual notify system if it can't
# talk to any of the UPS entries that are defined in this file. It will
# trigger a NOTIFY_NOCOMM by default every 300 seconds unless you
# change the interval with this directive.
NOCOMMWARNTIME 300
# --------------------------------------------------------------------------
# FINALDELAY - last sleep interval before shutting down the system
#
# On a master, upsmon will wait this long after sending the NOTIFY_SHUTDOWN
# before executing your SHUTDOWNCMD. If you need to do something in between
# those events, increase this number. Remember, at this point your UPS is
# almost depleted, so don't make this too high.
#
# Alternatively, you can set this very low so you don't wait around when
# it's time to shut down. Some UPSes don't give much warning for low
# battery and will require a value of 0 here for a safe shutdown.
#
# Note: If FINALDELAY on the slave is greater than HOSTSYNC on the master,
# the master will give up waiting for the slave to disconnect.
FINALDELAY 5
# --------------------------------------------------------------------------
# CERTPATH - path to certificates (database directory or directory with CA's)
#
# When compiled with SSL support, you can enter the certificate path here.
#
# With NSS:
# Certificates are stored in a dedicated database (splitted in 3 files).
# Specify the path of the database directory.
#
# CERTPATH /etc/nut/cert/upsmon
#
# With OpenSSL:
# Directory containing CA certificates in PEM format, used to verify
# the server certificate presented by the upsd server. The files each
# contain one CA certificate. The files are looked up by the CA subject
# name hash value, which must hence be available.
#
# CERTPATH /usr/ssl/certs
#
# See 'docs/security.txt' or the Security chapter of NUT user manual
# for more information on the SSL support in NUT.
# --------------------------------------------------------------------------
# CERTIDENT - self certificate name and database password
# CERTIDENT <certificate name> <database password>
#
# When compiled with SSL support with NSS, you can specify the certificate
# name to retrieve from database to authenticate itself and the password
# required to access certificate related private key.
#
# CERTIDENT "my nut monitor" "MyPasSw0rD"
#
# See 'docs/security.txt' or the Security chapter of NUT user manual
# for more information on the SSL support in NUT.
# --------------------------------------------------------------------------
# CERTHOST - security properties for an host
# CERTHOST <hostname> <certificate name> <certverify> <forcessl>
#
# When compiled with SSL support with NSS, you can specify security directive
# for each server you can contact.
# Each entry maps server name with the expected certificate name and flags
# indicating if the server certificate is verified and if the connection
# must be secure.
#
# CERTHOST localhost "My nut server" 1 1
#
# See 'docs/security.txt' or the Security chapter of NUT user manual
# for more information on the SSL support in NUT.
# --------------------------------------------------------------------------
# CERTVERIFY - make upsmon verify all connections with certificates
# CERTVERIFY 1
#
# When compiled with SSL support, make upsmon verify all connections with
# certificates.
# Without this, there is no guarantee that the upsd is the right host.
# Enabling this greatly reduces the risk of man in the middle attacks.
# This effectively forces the use of SSL, so don't use this unless
# all of your upsd hosts are ready for SSL and have their certificates
# in order.
# When compiled with NSS support of SSL, can be overriden for host
# specified with a CERTHOST directive.
# --------------------------------------------------------------------------
# FORCESSL - force upsmon to use SSL
# FORCESSL 1
#
# When compiled with SSL, specify that a secured connection must be used
# to communicate with upsd.
# If you don't use 'CERTVERIFY 1', then this will at least make sure
# that nobody can sniff your sessions without a large effort. Setting
# this will make upsmon drop connections if the remote upsd doesn't
# support SSL, so don't use it unless all of them have it running.
# When compiled with NSS support of SSL, can be overriden for host
# specified with a CERTHOST directive.
MONITOR salicru@127.0.0.1:3493 1 admin Localhost1977 master
#NOTIFYCMD /usr/local/ups/bin/notifyme.sh
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK "Communications with UPS %s established"
NOTIFYMSG COMMBAD "Communications with UPS %s lost"
NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"
NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"
NOTIFYMSG NOCOMM "UPS %s is unavailable"
NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"
NOTIFYFLAG ONLINE SYSLOG+WALL
NOTIFYFLAG ONBATT SYSLOG+WALL
NOTIFYFLAG LOWBATT SYSLOG+WALL
NOTIFYFLAG FSD SYSLOG+WALL
NOTIFYFLAG COMMOK SYSLOG+WALL
NOTIFYFLAG COMMBAD SYSLOG+WALL
NOTIFYFLAG SHUTDOWN SYSLOG+WALL
NOTIFYFLAG REPLBATT SYSLOG+WALL
NOTIFYFLAG NOCOMM SYSLOG+WALL
NOTIFYFLAG NOPARENT SYSLOG+WALL
# Network UPS Tools - upssched.conf sample file
#
# ============================================================================
#
# CMDSCRIPT <scriptname>
#
# This script gets called to invoke commands for timers that trigger.
# It is given a single argument - the <timername> in your
# AT ... START-TIMER defines.
#
# *** This must be defined *before* the first AT line. Otherwise the
# program will complain and exit without doing anything.
#
# A shell script with a big case..esac construct should work nicely for this.
# An example has been provided to help you get started.
CMDSCRIPT /bin/upssched-cmd
# ============================================================================
#
# PIPEFN <filename>
#
# This sets the file name of the FIFO that will pass communications between
# processes to start and stop timers. This should be set to some path where
# normal users can't create the file, due to the possibility of symlinking
# and other evil.
#
# Note: if you are running Solaris or similar, the permissions that
# upssched sets on this file *are not enough* to keep you safe. If
# your OS ignores the permissions on a FIFO, then you MUST put this in
# a protected directory!
#
# Note 2: by default, upsmon will run upssched as whatever user you have
# defined with RUN_AS_USER in upsmon.conf. Make sure that user can
# create files and write to files in the path you use for PIPEFN and
# LOCKFN.
#
# My recommendation: create a special directory for upssched, make it
# owned by your upsmon user, then use it for both.
#
# This is commented out by default to make you visit this file and think
# about how your system works before potentially opening a hole.
#
# PIPEFN /run/nut/upssched/upssched.pipe
# ============================================================================
#
# LOCKFN <filename>
#
# REQUIRED. This was added after version 1.2.1.
#
# upssched needs to be able to create this filename in order to avoid
# a race condition when two events are dispatched from upsmon at nearly
# the same time. This file will only exist briefly. It must not be
# created by any other process.
#
# You should put this in the same directory as PIPEFN.
#
# LOCKFN /run/nut/upssched/upssched.lock
# ============================================================================
#
# AT <notifytype> <upsname> <command>
#
# Define a handler for a specific event <notifytype> on UPS <upsname>.
#
# <upsname> can be the special value * to apply this handler to every
# possible value of <upsname>.
#
# Run the command <command> via your CMDSCRIPT when it happens.
#
# Note that any AT that matches both the <notifytype> and the <upsname>
# for the current event will be used.
# ============================================================================
#
# Possible AT commands
#
# - START-TIMER <timername> <interval>
#
# Start a timer called <timername> that will trigger after <interval>
# seconds, calling your CMDSCRIPT with <timername> as the first
# argument.
#
# Example:
# Start a timer that'll execute when any UPS (*) has been gone 10 seconds
#
# AT COMMBAD * START-TIMER upsgone 10
# -----------------------------------------------------------------------
#
# - CANCEL-TIMER <timername> [cmd]
#
# Cancel a running timer called <timername>, if possible. If the timer
# has passed then pass the optional argument <cmd> to CMDSCRIPT.
#
# Example:
# If a specific UPS (myups@localhost) comes back online, then stop the
# timer before it triggers
#
# AT COMMOK myups@localhost CANCEL-TIMER upsgone
# -----------------------------------------------------------------------
#
# - EXECUTE <command>
#
# Immediately pass <command> as an argument to CMDSCRIPT.
#
# Example:
# If any UPS (*) reverts to utility power, then execute
# 'ups-back-on-line' via CMDSCRIPT.
#
# AT ONLINE * EXECUTE ups-back-on-line
Dejo por último los distintos artículos/tutoriales en español que he consultado para aprender a configurar lo:
- https://www.jormc.es/tutoriales/administracion-basica-del-sai-salicru-spsone-900va-con-nut/
- https://www.jormc.es/2014/05/11/raspi-conectando-un-sai-salicru-sps-one-900va/